Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00053
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
09/27/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) BOND PANEL "A" ENCLOUSER 2.) INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMANAL. 3.) FILL UNUSED OPENINGS AT PANEL "A" 4.) USE FUSES AS SPECIFIED AND R CLIPS. 5.) TIGHTEN FLEX CONNECTOR 6.) BONDING DEVICES NEEDED AT SERVICES DISCONNECTS. | |
08/12/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*NO WORK PROGRESS UNIT IS BEING OCCUPIED FOR USE WITH OUT A FINAL INSPECTION OR C OF O. | |
07/11/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) EXIT LIGHTS CONDUIT TO BE SUPPORTED W/IN 3' OF BOX 2.) OUTSIDE LIGHT ABOVE SOUTH DOOR MISSING & EAST DOOR. 3.) AC UNITS #1 #2 #6 WIRE TO UNIT TO SMALL S/B #4 WITH LARGER GROUND THAN #10 #8. 4.) W/PROOF GFI ON ROOF MISSING. 5.) CHANGE ON WH'S NEED DISCONNECT FOR INSULATES 422 NEC 99 ALSO THEY LIST A 3000 W LOAD (25A) ON 20A CB 6.) ALL CONDUITS GOING TO [PNLA TO BE SUPPORTED 3' FROM PNL 7. PNL A 200 A MAIN BREAKER CALLED OUT BY PLAN 8.) PLAN SHOWS TIE IN TO 200 AMP FUSE DISCON IN SERVICE PNL NOT TO BUS VIOLATIONS LISTING OF SER ENT SECTION 9.) 2" CONDUIT TO 400A DISCON TO BE SUPPORTED PROPERLY NOT TIE WIRE FLEX NOT SUPPORTED ADD SUPPORT TO SW PROVIDE NAME OF ELECT.CONTR. FOLLOW UP. 30 DAYS. |