Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/10/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. READ THE MANUFACTURES DATA PLATE. YOU MUST LABEL THE DATA PLATE WITH THE PROPER HEATER KIT INSTALLED AND FUSE UNIT ACCORDINGLY. 2. A/C UNIT MUST SIT COMPLETELY ON A CONCRET PAD. BROKEN CHUNKS OF CONCRETE WILL NOT BE ACCEPTED. 3. FLEX DUCT MUST BE STRAPPED MIN. 4 APART. 1 1/2 WIDE STRAP MIN. FLEX CANNOT LAY ON THE GROUND 4. PAINT EXPOSED PVC W/SYNTHETIC LATEX PAINT. NO SPRAY PAINT. 5. INSTALL SHIELD BETWEEN HOUSE AND A/C UNIT TO PROTECT DUCT FROM WEATHER. |
| 05/10/2000 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |