Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/02/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* WORKING CLEARENCE VIOLATION 110-26 USE LISTED AND APPROVED PVC CONDUIT LOCK NUT ON BACKWARDS USE 2 GROUND RODS SPACED AS PER CODE NEED PERMANENT METAL ADDRESS LABEL USE CORRECT SUPPORT FOR CONDUIT USE ANTI-OXIDE COMPOUND ON ALUMINUM CONDUCTORS USE CORRECT FITTING ON RISE ABOVE SUB PANEL WILL NEED PERMIT FOR REWIRING OF HOUSE |