Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T00EL02571
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1) USE CORRECT BREAKERS AMPACITY FOR CONDUCTORS INSTALLED 2) VERIFY LICENCED ELECTRICAL CONTRACTOR 3) LABEL BREAKERS 4) USE CORRECT HUB LISTED BY MANUFACTURER 5) A REFEE HAS BEEN ISSUED | |
03/01/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* 1) COULD NOT VERIFY GAS PIPE BOND. 2) FITTINGS FOR CONDUIT TO HOUSE NEED TO BE RAIN TITE. 3) BREAKERS IN PANEL NEED TO BE SAME BRAND MAKE AS MANUFACTURER OF PANEL. 4) INSTALL BOND BUSHING ON 1" CONNECTOR 5) TEMP WIRE TO NEW SERVICE IS A SAFTEY ISSUE. HIRE OR GET A LICENCED CONTRACTOR TO DO JOB CORRECTLY OR POWER WILL BE DISCONNECTED PERMANENTLY. 6) 5 DAYS TO COMPLY | |
11/14/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* WILL NEED A LICENSED C-11 CONTRACTOR TO DO WORK ALL TO STRICLTY COMPLY WITH CODE IMPROPER WIRING METHOD USING NON RAINT EQUIPMENT NEEL PLAN |
|
11/02/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* NEED PERMANENT ADDRESS TAG METAL OR UNGROUND NEED GAS WATER BOND PARTIAL BOND AS BACKER TO MOUNT SERVICE IS NOT SUITABLE FOR THE ENVIROMENT |