Permit: T00EL02479

Parcel: 126100450


Addresses:

4432 E 6TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/05/2001 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
OK TO CLEAR
CALL FOR RE-INSPECTION (FINAL)
12/15/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
1-2 GROUND RODS REQUIRED AT 6' MIN SPACING
USE APPROVED FITTING TO CONNECT 1 1/2" LB TO PANEL ENCLOSURE
BOND WATER AND GAS PIPING SYSTEMS
PERMANENT ADDRESS TAG REQUIRED
ALSO NOTE THAT OWNER/OCCUPANT OF RESIDENCE IS DOING THE WORK