Permit: T00EL02456

Parcel: 113110630


Addresses:

1720 E EDISON ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T00EL02456

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
05/02/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
03/09/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999* 1) GROUND RODS TO BE 6' MINIMUM SPACING 2) NEED GAS BOND 3) NEED PERMANENT METAL ADDRESS LABELS 4) NEED 2 SUPPORT FOR RISER BELOW ROOF NEED 5) SEALING DEVICE FOR ENTRACES ABOVE BUSS 6) CANNOT CROSS IN FRONT OF BUSS WITH CONDUCTORS
7) LOOSE FITTINGS 8) SECURLY ANCHOR CONDUIT