Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 07/31/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1. ADDRESS SERVICE DO THE SAME FOR ADJACENT EXIST SERVICE 2. TAG ALL UNIT NUMBERS DO THE SAME FOR ADJACENT EXISTING 3. IMPROPER CLEARANCE IN FRONT OF SERVICE 4. REMOVE L.B. AND ELBOW FROM BOTTOM OF SERVICE PLUG HOLE 5. EXPOSE RODS GAS BOND MAKE GROUNDING ELECTRODE SYSTEM COMMON TO BOTH SERVICES 6. NEED AN ELECTRICAL PLOT PLAN AND INDICATE THE EXTENT OF NEW WORK |