Permit: T00EL01776

Parcel: 117041900


Addresses:

127 W 5TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00EL01776

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/24/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO RECONNECT
07/21/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1. NEED PERMANENT METAL ADDRESS LABEL
2. FILL HOLE WITH BLANK IN DEAD FRONT
3. BOND GROUNDING ELECTRODE RACEWAY 250-64 (A)
4. INCORRECT MAXIUM BREAKER HEIGHT 300-8
5. LABEL PANEL
6. NEED PERMIT FOR SERVICE UPGRADE
7. NEED LICENSED L-11 ELECTRICAL CONTRACTOR