Permit: T00CM06226


Addresses:

3009 N GAIA PL

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
02/07/2002 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*
02/05/2002 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*OK CABLE DROP ONLY DO NOT ENERIZE 1.) USE APPROVED FITTINGS TO CONNECT JUNCTION BOX FOR TEMP POWER OUTLET CHASE NIPPLE NOT APPROVED 1110-3. 2.)PLEASE CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUNDED TERMINAL 250-24. 3.) AMPACITY OF BREAKERS TO MATCH THAT OF THE CONDUCTOR FOR LOAD CARRIED 310. 4.) PLEASE VERIFY BOND IS POSTED.