Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/30/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 01/09/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK ROUGH ELECTRIC. |
| 01/08/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) USE REDUCING WASHER BOTH SIDES OF CONNECTOR AT PANEL. 2.) SMOKE DETECTOR TO BE 3' FROM REGISTRAR 3.) CONDUIT TO BE BURIED AS PER CODE 300-5 4.) ATTIC TO HAVE A LIGHT AND RECEPTACLE. 5.) PLEASE PROVIDE FHA STRAP ABOVE SUBPANEL BACKOUT 6.) SUPPORT PVC CONDUIT TO SUBPANEL. |
| 01/03/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/30/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) BOX FILL FOR DONDUCTORS IN FAN PAN OVER FILLED 370 2.) PROTECT CONDUCTORS AT BEAM AND STUDS 300-4. 3.) PLEASE PROVIDE GROUND FOR SWITCHES. 4.) GROUND ALL METAL BOXES. 5.) NEED TO HAVE WIRE CONNECTORS AT EXHAUST FANS 373-5 PANEL & METAL BOXES. 6.) FILL UNUSED OPENING IN BOXES. 7.)PANEL TO BE MADE UP AS PER MANUFACTURES SPECS. 8.) PLEASE PROVIDE FLEX FOR A/C & WATER HEATER STUBS. 9.) STRAP NM CABLE WITH IN 12" OF BOXES. |