Permit: T00CM06226


Addresses:

3009 N GAIA PL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/30/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
01/09/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK ROUGH ELECTRIC.
01/08/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) USE REDUCING WASHER BOTH SIDES OF CONNECTOR AT PANEL. 2.) SMOKE DETECTOR TO BE 3' FROM REGISTRAR 3.) CONDUIT TO BE BURIED AS PER CODE 300-5 4.) ATTIC TO HAVE A LIGHT AND RECEPTACLE. 5.) PLEASE PROVIDE FHA STRAP ABOVE SUBPANEL BACKOUT 6.) SUPPORT PVC CONDUIT TO SUBPANEL.
01/03/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
12/30/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) BOX FILL FOR DONDUCTORS IN FAN PAN OVER FILLED 370 2.) PROTECT CONDUCTORS AT BEAM AND STUDS 300-4. 3.) PLEASE PROVIDE GROUND FOR SWITCHES. 4.) GROUND ALL METAL BOXES. 5.) NEED TO HAVE WIRE CONNECTORS AT EXHAUST FANS 373-5 PANEL & METAL BOXES. 6.) FILL UNUSED OPENING IN BOXES. 7.)PANEL TO BE MADE UP AS PER MANUFACTURES SPECS. 8.) PLEASE PROVIDE FLEX FOR A/C & WATER HEATER STUBS. 9.) STRAP NM CABLE WITH IN 12" OF BOXES.