Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM06224
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
06/06/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1)NEED PROPER WORKING CLEARANCE IN FRONT OF A/C DISCONNECTORS. 2)LABEL MAIN BUS DUCT 400 AMP DISCONNECT. 3)IMPROPER WIRE BEND FOR TRANSFORMER FEEDER (200 HUP CIRCUIT BREAKER)NOTE: 600 MCM REQUIRES A MIN.DISTANCE OF 8".4)NEED PROPER BONDING AROUND 150 KVA TRANSFORMER GROUNDING ELECTRODE CONDUCTOR SLEEVE.5)REVISE PLAN.PLAN CALLS FOR NEUTRAL TO MAIN PANEL (AND OTHER AREA)-BUT THEIR IS 480 V.SYSTEM. |