Inspection History: ELECTRIC - FINAL

Permit Number - T00CM06224

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
06/06/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1)NEED PROPER WORKING CLEARANCE IN FRONT OF A/C DISCONNECTORS.
2)LABEL MAIN BUS DUCT 400 AMP DISCONNECT.
3)IMPROPER WIRE BEND FOR TRANSFORMER FEEDER (200 HUP CIRCUIT BREAKER)NOTE: 600 MCM REQUIRES A MIN.DISTANCE OF 8".4)NEED PROPER BONDING AROUND 150 KVA TRANSFORMER GROUNDING ELECTRODE CONDUCTOR SLEEVE.5)REVISE PLAN.PLAN CALLS FOR NEUTRAL TO MAIN PANEL (AND OTHER AREA)-BUT THEIR IS
480 V.SYSTEM.