Permit: T00CM05773

Parcel: 137335760


Addresses:

1900 W VALENCIA RD


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T00CM05773

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2001 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) OK TO COVER.
08/29/2001 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.)INSPECTED 8:00 AM NOT READY 2.)INSPECTED AGAIN AT 2:30 PM 3.) EXPOSE PIPING AND FITTINGS PAST CURB IN BOTH DIRECTIONS.
08/28/2001 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) YARDWATER COVERED BEFORE INSPECTION EXPOSE ALL FITTINGS AND PIPE FOR INSPECTION.
08/27/2001 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1.) YARDWATER FROM METER TO RPBP OK PRESSURE TEST OK 2.) EXPOSE YARDWATER FROM RPBP TO BLDG AND RECALL FOR INSPECTION. 3.) FUTURE STAB INTO MANHOLE #4 OK 40' FROM MANHOLE OK OK TO COVER.
08/23/2001 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) OK FOR TEMP POWER, PENDING ANY OTHER REQ'D INSPECTION 2.) I SIGNED OFF ON TEMP POWER SHEET.
06/18/2001 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1)2 1/2" WATER LINE STUBBED OUT OF BUILDING WITH COPPER TO VALVE IN BOX. 2 1/2" PVC GOES WHERE?
NO METER LOCATION, NO RPBP, NO INSPECTION ON BURIED 2 1/2" PVC SERVICE.
06/11/2001 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1)PVC UNDERGROUND OK 5# AIR TEST OK.2)OK TO COVER.3)YARD WATER STUB INTO BUILDING OK SIL-PHOS'D JOINTS UNDERSLAB OK.