Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T00CM05773
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
07/31/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PLUMBING WALLS ONLY IN TWO BATHROOMS MAY BE COVERED PVC DWV OK COPPER OK PRESSURE TEST OK 2.) INSTALL UNION ON DISCHARGE SIDE OF VALVE AT TRAP PRIMER. 3.0 REMEMBER, PLUMBERS TAPE AND TIE-WIRE NOT APPROVED. | |
07/26/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) FINAL CONNECTION BETWEEN BLDG DRAIN AND BLDG. SEWER OK WATER TEST OK 2.) ENTIRE DWV SYSTEM FILLED WITH WATER WATER TEST OK OK TO DRAIN. | |
07/25/2001 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
07/25/2001 | PLUMBING - INTERMEDIATE | Partial Approval | 1.) PVC DWV AT FRONT OFFICE OK WATER TEST WILL BE PERFORMED WITH REST OF BLDG. CONTRACTOR MAY COVER OFFICE WALLS ONLY WILL ASSUME LIABILITY FOR LEAKS. 2.) COPPER IN OFFICE TO ABOVE CEILING OK PRESSURE TEST OK OK TO COVER WALLS.3.) 6" C900 BLDG SEWER FROM BLDG DRAIN TO MANHOLE # OK WATER TEST OK OK TO DRAIN WILL NEED TO SEE FINAL CONNECTION TO BLDG DRAIN. |