Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T00CM05771

Parcel: 12205003C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T00CM05771

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/26/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* INSTALL SUPPORT WIRE TO SUPPORT LIGHTING TRACKS FROM STRUCTURES CEILING GRID NOT ALLOWED AS SOLE SUPPORT 300-11 NEC