Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* ELECT FINAL OK TO OPERATE EQUIPMENT INSTALL CIRCUIT BREAKERS COMPLING WITH PANEL LISTING ALL GE REQUIRED INSTALL PROTECTION WHERE CORD PENETRATE MACHINERY ENCLOSURE CORRECT ALL PANEL SCHEDULES AND APPROVED PLANS LEFT FOR OWNER HARD WIRE KIRSH DRILLING MACHINE COMING OFF POLE (HARDISON) |
|
| 01/19/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/18/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 01/16/2001 | ELECTRIC - FINAL | Denied | INSTALL ALL EQUIPMENT PER LISTING NEED CORRECTED WIRE SIZES ON EQUIPMENT NEED CORRECTED WIRING METHOD GROUNDING TERMNATION TO HAVE STA-KON TYPE OF TERMINATION. PLEASE PROVIDE PERMANENT DATA TAG 670-3 NEED COMPLETE ACURATE APPROVED PLANS FOR ALL CHANGES |
|
| 01/12/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* ALL EQUIPMENT TO BE U.L. LISTED AND INSTALLED PER MANUFACTURERS INSTRUCTIONS. USE APPROPRIATE GUTTER SIZE ALL CHANGES, CALCULATIONS ETC. MUST BE IN A CITY APPROVED REVISED PLAN WATCH DERATE. CORD NOT TO BE USED AS A PERMANENT WIRING METHOD EXCEPT FOR PORTABILITY OF 125 VOLT DROPS 15 OR 20 AMP |
|
| 01/09/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* MUST SEE WIRE ADAPTER INSTRUCTION/ LISTING FOR AL TO CU TERMINATION ADAPERTS ONLY 1. CRIMP INSTALLED NEED ACCESS TO BOXES FOR FLUORESCENT FIXTURES PANEL BOARDS (400 AMPS) NOT INSTALLED PER LISTING MAX WIRE SIZE 250 USED TO AL. IN VIOL OF 373- 6 (B) 1. NEED PERMANENT WIRING METHODS FOR MACHINERY NOT CORD AND PLUG NEED DISCONNECTS AND LISTED EQUIPMENT |