Permit: T00CM05608

Parcel: 13215003M


Addresses:

801 E 46TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/19/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
ELECT FINAL OK TO OPERATE EQUIPMENT
INSTALL CIRCUIT BREAKERS COMPLING WITH PANEL LISTING ALL GE REQUIRED
INSTALL PROTECTION WHERE CORD PENETRATE MACHINERY ENCLOSURE
CORRECT ALL PANEL SCHEDULES AND APPROVED PLANS LEFT FOR OWNER
HARD WIRE KIRSH DRILLING MACHINE COMING OFF POLE (HARDISON)
01/19/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/18/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
01/16/2001 ELECTRIC - FINAL Denied INSTALL ALL EQUIPMENT PER LISTING NEED CORRECTED WIRE SIZES ON EQUIPMENT NEED CORRECTED WIRING METHOD GROUNDING TERMNATION TO HAVE STA-KON TYPE OF TERMINATION. PLEASE PROVIDE PERMANENT DATA TAG 670-3
NEED COMPLETE ACURATE APPROVED PLANS FOR ALL CHANGES
01/12/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
ALL EQUIPMENT TO BE U.L. LISTED AND INSTALLED PER MANUFACTURERS INSTRUCTIONS.
USE APPROPRIATE GUTTER SIZE
ALL CHANGES, CALCULATIONS ETC. MUST BE IN A CITY APPROVED REVISED PLAN WATCH DERATE.
CORD NOT TO BE USED AS A PERMANENT WIRING METHOD EXCEPT FOR PORTABILITY OF 125 VOLT DROPS 15 OR 20 AMP
01/09/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
MUST SEE WIRE ADAPTER INSTRUCTION/ LISTING FOR AL TO CU TERMINATION ADAPERTS ONLY
1. CRIMP INSTALLED
NEED ACCESS TO BOXES FOR FLUORESCENT FIXTURES
PANEL BOARDS (400 AMPS) NOT INSTALLED PER LISTING MAX WIRE SIZE 250 USED TO AL. IN VIOL OF 373- 6 (B) 1.
NEED PERMANENT WIRING METHODS FOR MACHINERY NOT CORD AND PLUG NEED DISCONNECTS AND LISTED EQUIPMENT