Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 09/12/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Approved |
|
| 09/11/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Denied |
IVRS - Inspection 0245*/ NOTES: 1) SERVICE EQUIP. NOT INSTALLED PER PLAN. 2) BOND WIRE TO CT CAN BOND BUSHING TOO SMALL, SHOULD BE MIN. 1/0 CU. 3) CHECK AIC RATING ON PLAN, PANELS INSTALLED NOT RATED PER PLAN. DISCONNECTS DELETED BY CONTR. 4) REVISION NECESSARY BY ARCH MUST BE APPROVED AND STAMPED. 5) COMPLETE UNDERGROUND SECONDARY CONDUIT. |