Permit: T00CM05561

Parcel: 136048300

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
09/12/2003 ELECTRIC - TEMP POWER FOR TEST Approved
09/11/2003 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection 0245*/ NOTES: 1) SERVICE EQUIP. NOT INSTALLED PER PLAN. 2) BOND WIRE TO CT CAN BOND BUSHING TOO SMALL, SHOULD BE MIN. 1/0 CU. 3) CHECK AIC RATING ON PLAN, PANELS INSTALLED NOT RATED PER PLAN. DISCONNECTS DELETED BY CONTR. 4) REVISION NECESSARY BY ARCH MUST BE APPROVED AND STAMPED. 5) COMPLETE UNDERGROUND SECONDARY CONDUIT.