Permit: T00CM05561

Parcel: 136048300

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
09/17/2003 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR, BOND REQUIRED BEFORE CLEARANCE WILL BE SENT TO TEP
09/16/2003 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection 0000*
09/12/2003 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0210$/ 1) A REFEE IS DUE BEFORE NEXT INSPECTION 2) NEED GROUND BUSH AND BNOD JUMPER IN GUTTER FOR 2" WIPPLER 2) BOND RIGHT SIDE PANEL 3) NEED MAIN GROUND ELECTRICAL CONDUITS TO NEUTRAL BAR
09/04/2003 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection 0000* NOT READY NEED PERMANENT ADDRESS TAG METAL OR PLASTIC. SCREW OR RIVET IN PLACE . OPEN ??? AND PANEL BOARD. RECALL
08/27/2003 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*/1) NEED PERMANENT METAL ADDRESS TAG. 2) NEED GROUNDING, BUSHING AND BOND JUMPER AT BOTH SIDES OF NIPPLE/ C.T. CAN TO GUTTER. 3) OPEN GUTTER. 4) MUST ACCURATELY HAVE CITY APPROVED REVISION ON ELECTRICAL.
08/25/2003 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999* TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR( NEUTRAL CONDUCTOR). NEUTRAL LOOSE AT C.T. CABINET. INSTALL ADDRESS PER T.E.P.