Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/17/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO CLEAR, BOND REQUIRED BEFORE CLEARANCE WILL BE SENT TO TEP |
| 09/16/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 09/12/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0210$/ 1) A REFEE IS DUE BEFORE NEXT INSPECTION 2) NEED GROUND BUSH AND BNOD JUMPER IN GUTTER FOR 2" WIPPLER 2) BOND RIGHT SIDE PANEL 3) NEED MAIN GROUND ELECTRICAL CONDUITS TO NEUTRAL BAR |
| 09/04/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Not ready for Inspection |
IVRS - Inspection 0000* NOT READY NEED PERMANENT ADDRESS TAG METAL OR PLASTIC. SCREW OR RIVET IN PLACE . OPEN ??? AND PANEL BOARD. RECALL |
| 08/27/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*/1) NEED PERMANENT METAL ADDRESS TAG. 2) NEED GROUNDING, BUSHING AND BOND JUMPER AT BOTH SIDES OF NIPPLE/ C.T. CAN TO GUTTER. 3) OPEN GUTTER. 4) MUST ACCURATELY HAVE CITY APPROVED REVISION ON ELECTRICAL. |
| 08/25/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999* TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR( NEUTRAL CONDUCTOR). NEUTRAL LOOSE AT C.T. CABINET. INSTALL ADDRESS PER T.E.P. |