Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM05561

Parcel: 136048300

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/02/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*INTERIOR WIRING INTERMEDIATE. SUBJECT TO ENGINEER'S STAMPED LETTER ALLOWING THE USE OF ROMEX IN LIEU OF RACEWAY. FAX IS 791-3205
10/22/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*PLEASE ADDRESS THE FOLLOWING: 1.) THE ELECTRICAL SERVICE HAS BEEN CHANGED FROM THAT SHOWN ON PLAN SHT. E2. PANELS WITH REQUIRE MAIN. 2.) THE WIRING METHOD USED ROMEX IS NOT MENTIONED ON THE SPEC. SHEET. 3.) LIGHTING HAS BEEN CHANGED FROM 2 X 4 FLOURESCENT FIXTURES TO RECESSED LUMINAIRIES 4.) GROUNDING OF THE SERVICE EQUIPMENT IS INCOMPLETE. 5.) BONDING OF THE SERVICE IN INCOMPLETE 6.) EXHAUST FANS IN BATHS ARE NOT WIRED. THE ENGINEER OF RECORD MUST APPROVE THE CHANGES AND REVISE HIS PLANS. PLANS W/REVISIONS MUST BE REVIEWED AND APPROVED BY CITY PLANS REVIEWER. THE ELECTRICAL PANEL SCHEDULES AND LOAD CALCULATIONS WILL REQUIRE UPDATING TO REFLECT ANY LOAD CHANGES. THANKS MAC.