Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/02/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*INTERIOR WIRING INTERMEDIATE. SUBJECT TO ENGINEER'S STAMPED LETTER ALLOWING THE USE OF ROMEX IN LIEU OF RACEWAY. FAX IS 791-3205 |
| 10/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*PLEASE ADDRESS THE FOLLOWING: 1.) THE ELECTRICAL SERVICE HAS BEEN CHANGED FROM THAT SHOWN ON PLAN SHT. E2. PANELS WITH REQUIRE MAIN. 2.) THE WIRING METHOD USED ROMEX IS NOT MENTIONED ON THE SPEC. SHEET. 3.) LIGHTING HAS BEEN CHANGED FROM 2 X 4 FLOURESCENT FIXTURES TO RECESSED LUMINAIRIES 4.) GROUNDING OF THE SERVICE EQUIPMENT IS INCOMPLETE. 5.) BONDING OF THE SERVICE IN INCOMPLETE 6.) EXHAUST FANS IN BATHS ARE NOT WIRED. THE ENGINEER OF RECORD MUST APPROVE THE CHANGES AND REVISE HIS PLANS. PLANS W/REVISIONS MUST BE REVIEWED AND APPROVED BY CITY PLANS REVIEWER. THE ELECTRICAL PANEL SCHEDULES AND LOAD CALCULATIONS WILL REQUIRE UPDATING TO REFLECT ANY LOAD CHANGES. THANKS MAC. |