Permit: T00CM05529

Parcel: 128010010

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/16/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000* OK TO COVER WALLS
03/13/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999* 1) EACH DRAIN MUST HAVE ITS OWN TRAP PRIMER. 2) AN AREA DRAIN FOR A BATHROOM IS NOT APPROVED INDIRECT WASTE RECEPTICLE FOR A T AND P DRAIN
03/06/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1) FLOOR DRAINS OK TO COVER 2) THE LOCATION OF THESE DRAINS IS NOT THE BEST TUCKED IN BETWEEN WATER CLOSET AND BACK WALL AND SIDE WALL.