Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2000 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 11/27/2000 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* SIESMIC WIRES REQUIRED ON ALL LIGHTS FIXTURES CONDUIT REQUIRED TO BE SUPPORTED WITHIN 3' EACH BOX AND 10' INTERVALS PULL WIRE AND MAKE UP J-BOXES |
|
| 11/24/2000 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* |