Permit: T00CM05199

Parcel: 13405119G


Addresses:

9431 E 22ND ST #137

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
12/05/2000 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
11/27/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
SIESMIC WIRES REQUIRED ON ALL LIGHTS FIXTURES
CONDUIT REQUIRED TO BE SUPPORTED WITHIN 3' EACH BOX AND 10' INTERVALS
PULL WIRE AND MAKE UP J-BOXES
11/24/2000 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*