Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
Permit Number - T00CM05109
Inspection Description - ELECTRIC - TEMPORARY POLE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2001 | ELECTRIC - TEMPORARY POLE | Approved | IVRS - Inspection 0000* | |
04/19/2001 | ELECTRIC - TEMPORARY POLE | Denied | IVRS - Inspection 0999*1. CONDUIT COVERED PLEASE EXPOSE FOR INSPECTION 2. MORE THAN 360 DEGREE IN SINGLE ROW OF CONDUIT 3.CLEAN SURFACE BENEATH GROULD LUG 250-12 4. NEED TRANSFORMER OPENED FOR INSPECTION. |