Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/23/2001 |
ELECTRIC - TEMPORARY POLE |
|
Approved |
IVRS - Inspection 0000* |
| 04/19/2001 |
ELECTRIC - TEMPORARY POLE |
|
Denied |
IVRS - Inspection 0999*1. CONDUIT COVERED PLEASE EXPOSE FOR INSPECTION 2. MORE THAN 360 DEGREE IN SINGLE ROW OF CONDUIT 3.CLEAN SURFACE BENEATH GROULD LUG 250-12 4. NEED TRANSFORMER OPENED FOR INSPECTION. |