Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T00CM05106
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2001 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection 0000* | |
03/12/2001 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection 0000* 1) NEED TO SEE LAST SECTION OF PIPE INSTALLED AND FINAL CONNECTIONS TO METER 2) 100# TEST OK 3) 5441 HAS BEEN RE ENTERED INTO THE COMPUTER AS DENIED I NEED TO SEE PRESSURE TEST TO 100# AND THE REPAIRED SECTION LEFT OPEN FOR INSP. CALL WHEN READY | |
03/09/2001 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection 0999* 1) ARCHITECT REQUESTS A 100# TEST FOR FOUR HOURS PLEASE TEST BOTH BLDGS TO 100#'S AND CALL BACK FOR INSP. 2) OK TO BACK FILL 3) NEED TO SEE FINAL 10' OF PIPING AND FINAL CONNECTIONS TO METER. | |
03/08/2001 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection 0999* 1) PIPE COVERED BEFORE INSP. 2) UNABLE TO SEE PLASTIC TRANSITION AT COPPER 50# AIR TEST OK IF APPROVED TEST ON PLAN |