Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) REVISE MECHANICAL PLAN TO SHOW REQUIRED DUCT SIZES, PRESENTLY DUCTS 6" METAL 3 EACH WITH A SINGLE 6" RETURN 2) DUCT WORK MUST HAVE R 6 INSULATION 3) PROVIDE A MINIMUM OF 100 SQUARE INCHES HIG AND LOW COMBUSTION AIR 4) WATER HEATER REQUIRES 1/2" GAS CONNECTION 5) ELECTRIC WIRES IN MECHANICAL CLOSET NOT PROPERLY SECURED OR PROTECTED 6) COPPER WATER LINE CANNOT BE IN CONTACT WITH GALVANIZED DUCT WORK 7) TOILET VENT NOT PROPERLY INSTALLED 8) TOILET INCLOSURE TOO SMALL MUST HAVE 15" CLEARANCE TO EITHER SIDE 9) FIRE STOP ALL DROPPED CEILINGS 10) BATHROOM GFCI MUST BE ON DEDICATED 20 AMP CIRCUIT 11) DRYER CANNOT USE FLEX DUCT IN CEILING 12) SHEET METAL SCREWS NOT ALLOWED IN DRYER DUCT 13) LAUNDRY "P" TRAP TO HIGH 14) GROUND ALL METAL ELECTRIC BOXES |