Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 12/19/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ELECTRIC SPLICES NOT ALLOWED IN WALL CAVITY. MUST TERMINATE ALL WIRES IN AN ACCESSIBLE BOX, 2 LOCATIONS ON EAST WALL 2) GROUND ALL METAL ELECTRIC BOXES 3) ELECTRIC SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR MINIMUM #10 4) ELECTRIC SUB PANEL REQUIRES A GROUND WIRE 5) COLOR CODE NEUTRAL WIRE WHITE ON EACH END. OK TO INSULATE AND DRYWALL CEILING AND NORTH, SOUTH AND WEST WALLS. DO NOT COVER SPLICES IN EAST WALL |
| 09/07/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0950*/ 1) NOT READY |
| 09/05/2001 |
ELECTRIC - INTERMEDIATE |
|
Cancelled |
IVRS - Ri canceled |