Permit: T00CM04293

Parcel: 14125004B


Addresses:

9533 S WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/28/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/22/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0215*
THE NEC REQUIRES EACH CABLE TO BE TERINATED IN ITS OWN TERMINAL LUG, THE GARGED WIRES AT BOTH MAIN SWITCHES ARE NOT ACCEPTABLE.
IF YOU HAVE THE MANUFACTURS DESCRIPTION, SPEC'S , U/L LISTING ETC, ALLOWING GAUGING OF WIRES IN THE INSTALLED LUGS PLEASE PRESENT THIS INFO TO MR. RANDY SCHULER AT COT- DSC FOR HIS REVIEW AND APPROVAL, PROVIDE STAMPED FOR HIS REVIEW AND APPROVAL, PROVIDE STAMPED COPY ON SITE FOR THIS INSPECTOR
12/18/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*