Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T00CM04282
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2000 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
09/19/2000 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0935* MC CABLE NOT SUPPORTED (CONF RM) ABOVE NEW QUAD OUTLET REMOVE TILE OVER ALL NEW SWITCHES AND RECEPTACLE LOCATIONS FOR PROPER ABOVE CEILING INSPECTION. LOOSE J-BOXES NOT SUPPORTED ABOVE PARTION CONF RM THIS IS THE 3RD ABOVE CEILING INSP PAY RE-FEE PRIOR TO FUTURE INSPECTIONS |
|
09/18/2000 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* CONDUIT SUPPORTS NEED TO BE INSIVIDAUL STRAPPING TO GRID WIRES NOT ALLOWED UNDER 99' NEC. CITY OF TUCSON ADD'S |
|
09/14/2000 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* CONDUIT, J-BOXES AND ASSOCIATED WIRING FOR NEW CIRUCITING NOT COMPLETE DO NOT COVER UP CEILING WITH TILE TILL INSPECTED |