Permit: T00CM04027

Parcel: 129090020

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/09/2001 ELECTRIC - FINAL Denied AFTER HOURS INSP: 1) 1-200 AMP SERVICE DISCONNECT INSIDE - NOT GROUNDED WITH OTHER SERVICE DISCONNECT. 2) NOT WIRED ACCORDING TO PLAN 3) 600 AMP DISCONNECT BOND NEUTRAL, LACKS 1 NEUTRAL, CALLS FOR PARALLEL CONDUIT TO DISCONNECT AND TO SUB PANEL. INSTALL SEALING LOCK NUTS, CHECK FOR FUSE EQUIVALENCY PER PLAN. PARALLELING REQUIRED TO PANEL A.C. MARK A/C DISCONNECT, NEED SEALING LOCK NUT, NEED BUSHING. BOND A/C DISCONNECT ID ALL PORCH DISCONNECT PLEASE DOUBLE CHECK ALL ITEMS EG:WIRE BOND RADIUS AND OTHER CODES BEFORE NEXT INSP.
12/14/2000 ELECTRIC - FINAL Partial Approval OK FOR TEMP C/O IVRS - Inspection 0000*
12/12/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
NEW PAENL 'N' ELIMINATED
HEAT PUMPS AND OTHER CIRCUITS COMBINED ONTO OTHER PANELS/DISCONNECTORS
I MUST SEE A CITY APPROVED REVISED PLAN, MUST ACCURATELY DEPICT AS BUILT WIRING. INCLUDE ONE LINE DIAGRAM, PLAN, SERVICE, LOCATIONS,ETC