Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/02/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/01/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* |
| 07/27/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) MARK PERMANENTLY A/C DISCONNECTS 2.) THE CLEARANCE IN FRONT OF THE A/C DISCONNECTS IN VIOLATION OF 110-26. 3.) EXIT LITES WIRING METHODS TO COMPLY W/ART 501 ETC. NEED SEAL OFF GOING INTO UNCLASSIFIED AREA, NEED GROUND. BUSH AND BOND JUMPERS AT ALL INTERVENINT RACEWAY SEE 501-16. 4.) NEED ALL SCREW TO SUPPORT RECEPTACLE INDUSTRIAL RAISED COVERS. |