Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM03704
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
08/01/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* | |
07/27/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) MARK PERMANENTLY A/C DISCONNECTS 2.) THE CLEARANCE IN FRONT OF THE A/C DISCONNECTS IN VIOLATION OF 110-26. 3.) EXIT LITES WIRING METHODS TO COMPLY W/ART 501 ETC. NEED SEAL OFF GOING INTO UNCLASSIFIED AREA, NEED GROUND. BUSH AND BOND JUMPERS AT ALL INTERVENINT RACEWAY SEE 501-16. 4.) NEED ALL SCREW TO SUPPORT RECEPTACLE INDUSTRIAL RAISED COVERS. |