Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00CM03689
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/09/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*1)LIGHT FIXTURES TO BE FULLY SHEIDED-4 AT SOUTHSIDE.DO PREVIOUS INSPECTION THAT ARE NOTED AS NOT DONE OK ROOM #120,121.CHECK SERVICE NEXT INSPECTION. | |
04/25/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK TO COVER WALLS | |
04/24/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
04/18/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS RM# 130, 120 PROTECT DATA RUN VERTICAL ALONG WEST WALL CAN NOT RUN IN SHEVING |
|
04/17/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*PLEASE CALL FOR ABOVE CEILING INSPECTION, 02036, HAVE TILES OPEN FOR INSPECTION. ALL AREAS NEED TO HAVE FINAL INSPECTION BEFOR OCCUPANCY. | |
04/05/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) MISSING WEATHER PROOF COVER TOP OF POLE 2) CORRECTLY ID GROUNDING EQUIPMENT CONDUCTOR 3) ID CONDUCTORS CORRECTLY | |
03/23/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) GROUND 4 SQ BOXES ON HIGH BAY LIGHTS 2) ADJUST TO LEVEL HIGH BAY LIGHTS 3) TIGHTEN LOCKNUTS ON LIGHTS 4) ID GROUNDING CONDUCTOR AT LIGHT POLES 5) INSTALL LIGHT BULBS CORRECTLY 6) ID CONDUCTORS CORRECTLY AT FIXTURES POLE 2110-5C CITY ORDINANCE #9287 |
|
03/14/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) OK WAL AS MARKED ON PLAN. 2) OK OUTSIDE CONDUITS ON SHOWROOM WALLS. 3) NEED FINAL INSP. CALLED FOR AREAS OCCUPIED BY 3-15-01 | |
03/10/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | AFTER HOURS INSP:OK WALLS AS MARKED ROOM#'S 140-107, 101,141 AND PARTIAL ON 125 | |
03/02/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* TEMP C OF O BOND TO BE POSTED BY 3:00PM MARCH 6 OR JOB WILL BE LOCKED DOWN. OK 113 AND 180 AS MARKED ON OFFICE PLANS | |
02/27/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) UNDERGROUND IN EXITING SHOWROOM OK 2) WALLS AS MARKED 126,138, AND 137 OK 3) SERVICE CROSS OVER SUBJECT TO POSTING OF BOND NEED INSP TO OCCUPY OFFICE AND SERVICE ADVISOR AREA ALSO SUBJECT TO POSTING OF BOND | |
02/02/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK CUSTOMER SERVICE CEILING FANS | |
02/01/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK UNDERGROUND TO SERVICE ADVISOR WALL OK WALLS AS MARKED ON PLANS OK HARDCEILING #124 EXCEPT FANS |
|
01/29/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* CHECK FOR SATURDAY TO BE DROPPED OFF AT DSC |
|
01/28/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS AS MARKED ON OFFICE PLAN SERVICE ADVISOR AND CASHIER |
|
01/25/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK CONDUIT PANEL TO 10' SHORT OF GRID LINE #12 OK CONDUITS IN PANEL ROOM |
|
01/15/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS ROOM # 110, 112 EXCEPT EAST WALL |
|
01/11/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK EMT-BOX UP TO 18' |
|
01/09/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* ALL CELLS WITH ELECTRIC INSTALLED HAVE BEEN GROUTED, ALL UNDER GROUND INSTALLED WITHOUT INSPECTION, ALL BOXES INSTALLED IN MASONARY WITHOUT INSPECTION, NOT AVALIBLE FOR USE |