Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* NOTE: PANEL SHOULD BE LABELED ON OUTSIDE OF COVER FOR EASY RECOGNITION | |
| 03/28/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) PANEL "A" FUSES NOT AS LISTED ON PLAN-ALSO DO NOT CROSS TO SAME STYLE AS LPN-R 2) FINISH PREVIOUS LIST AND ENERGIZE FOR INSP. | |
| 03/27/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) LABEL SUB PANEL A OR B ? 2) NEED PANEL SCHEDULE EXSISTING PANEL AND LABEL A OR B? 3) LABEL A/C DISCONNECTS 4) NEED FULL SET OF PLANS ON SITE 5) PLEASE FINISH WORK |
|
| 02/26/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |