Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T00CM03657

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2000 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
09/18/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
ADDITOINAL CONDUIT SUPPORT REQUIRED
MC CABLE WITHIN 1' OF EVERY J-BOX AND AT 6' INTERVALS
EMT CONDUIT WITHIN 3' EVERY J-BOX AND 10' INTERVALS
EXCLUDED ARE FIXTURE SHIPS 6' LONG OR LESS
MUST HAVE OWN CEILING WIRE IF USED TIED OH AT BOTH ENDS
DO NOT USE GRID WIRE INTENDED TO SUPPORT GRID