Permit: T00CM03058

Parcel: 123040870


Addresses:

3017 E LINDEN ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
04/18/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
04/09/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. OS.B. MUST BE INSTALLED PERPENDICULAR TO RAFTERS/TRUSSES 4 SHEETS INSTALLED PARALLEL. 2. OVER BUILT ARE REQUIRES STRINGER/VALLEY BOARD UNDER ENDS BEARING ON EXISTING ROOF SHEATHIN. 3. U 24 HANGERS REQUIRED AT RAFTER CONNECTION TO TRUSS. 4. YOU MUST PROVIDE CITY OF TUCSON APPROVE TRUSS DRAWINGS. 5. SOUTH TRUSS HAS BEEN CUT/NOTCHED IN EXCESS OF 50% 2 PLACES. PROVIDE CITY OF TUCSON AND TRUSS ENGINEERS APPROVED REPAIR. 6. WINDOWS ARE NOT PER PLAN AND DO NOT MEET MODEL ENERGY CODE REQUIREMENTS. REVISE PLAN TO AS BUILT AND HAVE PLAN SPECIFY WINDOW "U" VALUE REQUIREMENTS. 7. BEARING STUD IN CLOSET CUT AND SPLICED REPLACE. 8. 2 X 3 HEADER UNDERSIZE AT CLOSET 4010 WINDOW. 9. KING STUDS REQUIRED BY WINDOW TRIMMERS. 10. X BRACE 3 TRUSSES AT EACH END OF ROOF AT RIDGE. 11. PROVIDE ENGINEERING APPROVAL FOR SOUTH TRUSS TO BE USED AS GIRDER. 12. BLOCK BETWEEN TRUSSES AT SKYLIGHT.
04/06/2001 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection