Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T00CM03035
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2001 | FRAMING | Approved | ||
06/22/2001 | FRAMING | Denied | IVRS - Inspection 0950*/ 1) NOT READY, NO CHANGE CONFERENCE | |
06/14/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) LAUNDRY MUST HAVE A MINIMUM 2" DRAIN SYSTEM WITH 1 1/2" VENT SYSTEM, PRESENTLY DRAIN IS 1 1/2" TO SMALL 2) BATHROOM MUST HAVE EXHAUST FAN 3) WATER HEATER MUST HAVE 100 SQUARE INCHES HIGH AND LOW VENTILATION, SEE A-3 4) CLOTHES DRYER MUST HAVE A 4 WIRE CIRCUIT WITH 4 WIRE OUTLET NOTE: STUCCO LATH MUST HAVE 2 LAYERS OF VAPOR BARRIER | |
06/13/2001 | FRAMING | Denied | ||
09/27/2000 | FRAMING | Partial Approval | IVRS - Inspection 0000*/FRAME OK BUT CANNOT CLEAR UNTIL PLUMBING AND MECH ARE COMPLETE. | |
09/06/2000 | FRAMING | Denied | IVRS - Inspection 0999* |