Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/29/2001 |
FRAMING |
|
Approved |
|
| 06/22/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) NOT READY, NO CHANGE CONFERENCE |
| 06/14/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) LAUNDRY MUST HAVE A MINIMUM 2" DRAIN SYSTEM WITH 1 1/2" VENT SYSTEM, PRESENTLY DRAIN IS 1 1/2" TO SMALL 2) BATHROOM MUST HAVE EXHAUST FAN 3) WATER HEATER MUST HAVE 100 SQUARE INCHES HIGH AND LOW VENTILATION, SEE A-3 4) CLOTHES DRYER MUST HAVE A 4 WIRE CIRCUIT WITH 4 WIRE OUTLET NOTE: STUCCO LATH MUST HAVE 2 LAYERS OF VAPOR BARRIER |
| 06/13/2001 |
FRAMING |
|
Denied |
|
| 09/27/2000 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/FRAME OK BUT CANNOT CLEAR UNTIL PLUMBING AND MECH ARE COMPLETE. |
| 09/06/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |