Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T00CM02109
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2001 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* GAS PRESSURE TEST OK 15# GS PIPING OK VALVES AND CONNECTIONS OK |
|
01/22/2001 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999* STILL NEED HORIZONTAL SUPPORT AT ROOF DRAINS RPBP TURNED BACK TO TRUE OK COPPER PIPE AT WAER HEATER TOUCHING RUN PAN DRAIN AND T&P SEPARATE AND FULL SIZE TO JANITORS SINK ONLY ONE SLIP NOT ALLOWED ON OUTLET OF P-TRAP SUPPORT CONDENSATE DRAIN AT JANITORS SINK URINAL AT WRONG ELEVATION LAVATORIES AT INCORRECT HEIGHT 18" MINUMUM FROM SIDEWALL TO CENTER OF H.C. WATER CLOSET NEED TO SEE 10# AIR TEST ON GAS LINES WILL NOT APPROVE BLOCKING ON GAS LINES WILL NOT APPROVE BLOCKING ON GAS PIPE ADD 2 HOLE STRAPS WHERE NEEDED CHANGE OVERSIZED 2 HOLE STRAPS TO CORRECT SIZE (SEE DETAIL M-2) CONDENSATE DRAINS NOT TO PLAN THIS MAY NOT INCLUDE ALL CODE VIOLATIONS PLEASE CHECK YOUR ENTIRE JOB BEFORE CALLING BACK IN |