Inspection Status: Denied
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T00CM02109
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2000 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* | |
10/09/2000 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* WATER TEST OK TRAP ARMS CHANGED OK TRAP PRIMER OK OK TO COVER |
|
10/06/2000 | PLUMBING - ROUGH, SOIL | Denied | AGAIN 1003.3 PLEASE READ THE LAST SENTENCE THE TRAP SHALL BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS CONNECTED PLEASE MAKE THIS CORRECTION IN ALL AREAS IF APPLIES |
|
10/04/2000 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* | |
10/03/2000 | PLUMBING - ROUGH, SOIL | Denied | SEE 1003.3 94 UPC THE TRAP AND TRAP ARM SHALL BE THE SAME SIZE 2. SEE 706.2 DOUBLE SANTEES MAY BE USED WHEN THE BARREL OF THE FITTING IS 2 PIPE SIZES LARGER THAN THE LONGEST INLET DON'T FORGET TRAP PRIMERS AND WRAPPED PIPE |
|
10/02/2000 | PLUMBING - ROUGH, SOIL | Partial Approval | PLEASE 3" WASTE FOR FLOOR DRAINS AS PER APPROVED PLAN RE TEST AND CALL AGAIN/ DON'T FORGET TRAP PRIMERS AND WRAP |