Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2001 | ELECTRIC - UNDERGROUND | Denied | TEMP POWER FUEL AND TEST ADDRESS SERVICE CHANGE LUGS TO ACCEPT CORRECT WIRE RANGE RE TORQUE ALL CONDUCTORS PER. MANUFACTURE'S SPECIFICATION ATTACH MAIN BONDING JUMBER INSERT WIRE FULLY INTO LUG WILL NEED TO RESOLVE 1 SPARE 4" CONDUIT INTO SERVICE (SPARE) BEFORE FINAL |
|
| 12/27/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* UNDERGROUND CONDUIT COMPLETE CALL FOR UNDERGROUND WHEN READY |
|
| 12/20/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* SITE LIGHTING PARTIAL NORTH SIDE NORTH EAST EAST SIDE |
|
| 12/15/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* 8 POLE BASER GROUNDING INTO BASE AND STUB OUT |
|
| 12/01/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* SUMP PUMP UNDERGROUND APPROVED |
|
| 11/16/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* 2-4" SECONDARY FROM END OF SOUTH EAST TO SOUTH WEST CORNER APPROVED WEST, EAST AND SOUTH EAST AND STORAGE WELL ROUGH APPROVED |
|
| 10/26/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* | |
| 10/18/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* OK TO CLEAR UNDERGROUND CONDUIT NORTH FRNT (WEST) PARTIAL |
|
| 10/11/2000 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* 'B' LINE UNDERGROUND RECEPT AND BOX APPROVED |