Permit: T00CM01979

Parcel: 21116006A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/09/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/01/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) SEAL UNUSED OPENING 2) USE CORRECT SIZED WIRE FOR SURGE ARRESTERS AS PER PLAN AND USE FUSE/BREAKER ACCORDING TO CONDUCTOR SIZE 3) DBL LUGING MAIN BREAKER-PANEL 4) SUPPORT CONDUITS (BELOW PANEL, THROUGHOUT) AS PER CODE 5) CLORINE STATION LOCKED NO ACCESS 6) PROVIDE PROTECTION FOR SEAL TITE THROUGH METAL CASE 7) LOOSE SEAL TITE FITTWLS