Permit: T00CM01978

Parcel: 21116006A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/09/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/01/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/1) SUPPORT CONDUITS IN AND OUT OF TRANSFORMER 2) SUPPORT CONDUITS BELOW PANEL 3) LOOSE SEAL TITE FITTINGS 4) DBL LUGGING PANEL MAN BREAKER 5) USE PROPER FUSE/BREAKER ACCORDING TO CONDUCTOR SIZE 6) SUPPORT PVC CONDUIT AS PER CODE 7) PROVIDE PROTECTION FOR SEAL TITE THROUGH METAL CASE