Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/09/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/01/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) SUPPORT CONDUITS IN AND OUT OF TRANSFORMER 2) SUPPORT CONDUITS BELOW PANEL 3) LOOSE SEAL TITE FITTINGS 4) DBL LUGGING PANEL MAN BREAKER 5) USE PROPER FUSE/BREAKER ACCORDING TO CONDUCTOR SIZE 6) SUPPORT PVC CONDUIT AS PER CODE 7) PROVIDE PROTECTION FOR SEAL TITE THROUGH METAL CASE |