Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/07/2000 |
BUILDING - FINAL |
|
Partial Approval |
PARTIAL APPROVAL |
| 04/05/2000 |
BUILDING - FINAL |
|
Correction Required |
ADDTL COMMS - DENIED - 1. NEED PERMIT FOR GAS LINE. 2. NEED LETTER FROM HOMEOWNER STATING THAT THE GAS LINE TRENCH IS 18 DEEP WITH A CONTINUOUS TRACER WIRE. INDICATE THE TYPE OF GAS PIPING USED. ALSO STATING THAT AN APPROVED TRANSITION FITTING WAS USED. 3. I.D. SPA BREAKER. (SPA IS NOT ON SITE FOR INSPECTION. REQUIRED BREAKER SIZE UNKNOWN AT THIS TIME). 4. NEED PRESSURE TEST ON GAS LINE. 10-LBS. FOR 15 MINUTES. 5. PROVIDE A HOSE BIBB BACKFLOW DEVICE ON NEW HOSE BIBB. 6. ITEM #2. INCLUDE WATER LINE IN THE LETTER. BURIAL DEPTH AND TYPE OF MATERIAL. 7. AT SUB-PANEL SEPARATE NEUTRALS AND GROUNDS. ONE CONDUCTOR PER LUG. 8. ONE GFI PROTECTED OUTLET REQUIRED. 10-20 FROM POOL/SPA. 9. BOND ANY METAL WITHIN 5 OF SPA. |
| 04/05/2000 |
BUILDING - FINAL |
|
Denied |
MULT. CORRECTIONS SEE F6 |