Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
Permit Number - T00CM01377
Inspection Description - ELECTRIC - TEMPORARY POLE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2001 | ELECTRIC - TEMPORARY POLE | Approved | ||
12/27/2000 | ELECTRIC - TEMPORARY POLE | Partial Approval | IVRS - Inspection 0000* | |
12/26/2000 | ELECTRIC - TEMPORARY POLE | Partial Approval | IVRS - Inspection 0000* MAIN SERVICE CORRECTIONS MADE SECURE SERVICE STAND FROM TIP OVER OR BLOW OVER TRANSFORMER AND PANEL NOT READY |
|
12/21/2000 | ELECTRIC - TEMPORARY POLE | Denied | PUT AN ADDRESS ON SERVICE CORRECT 4: PVC CONNECTOR AT BOTTOM OF CT CAN 50 LOCK NUT TIGHTENDS DOWN FIRMLY TWO GROUND RODS REQUIRED USE A GROUDNING BUSHING ON 4" NIPPLE INSIDE 600 AMP SWITCH BOTH SIDES REQUIRED ON A SERVICE 600 AMP FUSE TOO BIG FOR 3/0 ALUM PROPERLY ATTACH 2" PVC AT BOTTOM OF SWITCH USE RE WASHER 2" PVC SHOULD BE SCH 80 2" PVC BOTTOM OF SWITCH OVERFILLED ONLY 5 3/0s OUT INSTALL A JUMPER FROM GROUND ELECTRODE CONDUTOC IN TRANS TO NEUTRAL STRAP DOES NOT SURFACE HERE COVER OPEN HOLES IN SUB-PANEL SEAL OPEN BREAKER SLOTS AND SUPPORT GFI BOX TO WEST CANNOT HANG OFF CONNECTOR AS ONLY MEANS |