Inspection History: ELECTRIC - TEMPORARY POLE

Permit Number - T00CM01377

Inspection Description - ELECTRIC - TEMPORARY POLE

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2001 ELECTRIC - TEMPORARY POLE Approved
12/27/2000 ELECTRIC - TEMPORARY POLE Partial Approval IVRS - Inspection 0000*
12/26/2000 ELECTRIC - TEMPORARY POLE Partial Approval IVRS - Inspection 0000*
MAIN SERVICE CORRECTIONS MADE
SECURE SERVICE STAND FROM TIP OVER OR BLOW OVER
TRANSFORMER AND PANEL NOT READY
12/21/2000 ELECTRIC - TEMPORARY POLE Denied PUT AN ADDRESS ON SERVICE
CORRECT 4: PVC CONNECTOR AT BOTTOM OF CT CAN 50 LOCK NUT TIGHTENDS DOWN FIRMLY
TWO GROUND RODS REQUIRED
USE A GROUDNING BUSHING ON 4" NIPPLE INSIDE 600 AMP SWITCH BOTH SIDES REQUIRED ON A SERVICE
600 AMP FUSE TOO BIG FOR 3/0 ALUM
PROPERLY ATTACH 2" PVC AT BOTTOM OF SWITCH USE RE WASHER
2" PVC SHOULD BE SCH 80
2" PVC BOTTOM OF SWITCH OVERFILLED ONLY 5 3/0s OUT
INSTALL A JUMPER FROM GROUND ELECTRODE CONDUTOC IN TRANS TO NEUTRAL STRAP DOES NOT SURFACE HERE
COVER OPEN HOLES IN SUB-PANEL SEAL OPEN BREAKER SLOTS AND SUPPORT GFI BOX TO WEST CANNOT HANG OFF CONNECTOR AS ONLY MEANS