Permit: T00CM01377

Parcel: 13705505D


Addresses:

1225 W IRVINGTON RD

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
01/05/2001 ELECTRIC - UFER Approved IVRS - Inspection 0000*
UFER 20 FT MIN AND ON 30' MIN REBAR X-OTHER WISE WELD AND MECHANICALLY CONNECTED
01/03/2001 ELECTRIC - UFER Denied IVRS - Inspection 0999*
PLEASE ATTACH TO BOTTOM REBAR
01/02/2001 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection 0000*