Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2001 | ELECTRIC - UFER | Approved | IVRS - Inspection 0000* UFER 20 FT MIN AND ON 30' MIN REBAR X-OTHER WISE WELD AND MECHANICALLY CONNECTED |
|
01/03/2001 | ELECTRIC - UFER | Denied | IVRS - Inspection 0999* PLEASE ATTACH TO BOTTOM REBAR |
|
01/02/2001 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection 0000* |