Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T00CM01217

Parcel: 128010010

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T00CM01217

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/25/2000 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
ALL CORRECTIONS HAVE BEEN MADE
09/08/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
INSTALL CONDENSATE DRAIN
LABEL DISCONNECT W/PROPER CIRCUIT NUMBER MUST BE PERMANENT (40 MAX)
TUR-2
PERMANENTLY LABEL UNIT AND DISCONNECT
INSTALL CONDENSATE DRAIN
MARK DATA PLATE W/PROPER HEAT STRIP
CIRCUIT BREAKER TOO SMALL CHECK UNIT DATA PLATE
RTU-3
PERMANENTLY LABEL LUNIT AND DISCONNECT
INSTALL CONDENSATE DRAIN (45 MAX)
CIRCUIT BREAKER TOP SMALL CHECK UNIT DATA PLATE