Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/18/2018 |
BUILDING - FINAL |
|
Approved |
|
| 10/05/2000 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*1. ALL COUNTER ELECTRIC OUTLETS IN KITCHEN MUST BE GFCI PROTECTED SOUTH AND EAST WALLS DO NOT COMPLY. 2. ELECTRIC OUTLET (GFCI) REQUIRED ON ALLCOUNTER TOPS IN EXCESS OF 12" WIDE IN KITCHEN. 3. ELECT OUTLET LOOSE AT WEST END OF SOUTH KITCHEN WALL. 4. WINDOW WITHIN 24" OF FAMILY ROOM DOOR MUST BE SAFETY GLAZED. ALSO BEDROOM 3 AND 4 WINDOWS. 5. BEDROOM SMOKE DETECTORS CANNOT BE WITHIN 36" OF AIR REGISTERS. 6. YOU MUST PROVIDE LADDER ACCESS TO ATTIC FURNACE. |
| 09/15/2000 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/CITY ORDINANCE REQUIRES THE HOUSE ADDRESS BE POSTED ON THE HOUSE AT A PLACE VISIBLE FROM THE STREET. MINIMUM SIZE NUMBERS OF 3" HIGH. RECALL INSPECTIONS AND ARRANGE TO BE HOME. |