Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/23/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED FRAMING FOR CEILING FAN |
| 09/21/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) LOWER COLLAR TIES TO 1/3 SPAN 2) DOUBLE 2 X 10'S CUT/RIPPED MUST BE FULL 2-2 X 10'S 3) EM CENTER LINE NOT ALLOWED IN CONDUIT 4) RAFTER OVER SPANNED SOME 27" ON CENTER 5) BLOCK 3 SIDES AIR GRILLS 6) ACCESS TO AIR HANDLER SHALL NOT BE OBSTRUCTED 7) NEED APPROVAL ON AIR HANDLER DECK 8) DOUBLE 2 X 10 SHALL NOT BE SPLICED 9) 2" CLEARANCE REQUIRED FROM COMBUSTIBLE AT FIREPLACE CHIMNEY |