Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/12/2001 |
STEM WALL/RETAINING WALL |
|
Approved |
IVRS - Inspection 0000* |
| 10/10/2001 |
STEM WALL/RETAINING WALL |
|
Denied |
IVRS - Inspection 0999*NEED LETTER FROM ARCHETECT SPECIFYING HOW TO FIX STEM WALL WHERE BED JOINT IS MORE THAN 1" THICK. |
| 10/05/2001 |
STEM WALL/RETAINING WALL |
|
Denied |
IVRS - Inspection 0999*1.) UBC 2106.1.6. INITAL BED JOINT MAY NOT 2104.4.1 BE MORE THAN 1" THICK 2.) UBC 2104.4.2. LOOSE MATERIAL IN GROUT CELLS MUST BE CLEANED OUT 3.) MORTAR FINS MAY NOT EXTEND INTO GROUT CELL MORE THAN 1/2" |