Permit: T00CM00340

Parcel: 128010010


Addresses:

5870 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/21/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE.
11/09/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*CONDENSATE DRAIN TO AH-1 MUST BE SAME SIZE AS OUTLET ON UNIT. CANNOT BE REDUCED TO 3/4" PLUG EXTRA OUTLET ON AH 1 & 2. LOCATE SECONDARY PAN UNDER UNIT ON AH-2.
10/19/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*REMOVE UNION FROM GAS PIPE ON ROOF TO RUBIOS 2 UNITS ON ROOF SE-1 & SE-2 DUCT NOT INSULAED. STILL NEED TO SEE 2 AIR HANDLERS.
08/07/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
08/06/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) FINISH CONDENSATE DRAINS ON ROOF. 2.) NEED TO SEE CONDENSATE DRAINS ON WALK IN COOLERS LABEL CONDENSORS ON ROOF FOR ICE MACHINES. 3.) PROVIDE SMOKE DETECTOR TO FCU 3 & 4 4.) HOOK UP CONTROL WIRING TO FCU 1 & 2 OK FOR C OF O IN ALL THEATERS. NEED TO SEE AIR HANDLER ABOVE OFFICES.
07/13/2000 MECHANICAL - FINAL Partial Approval OK FOR TEMP C OF O STILL NEED TO SEE A/C SYSTEM IN OFFICE & SOUTH EXIT CORRIDOR NEED TO SEE PROPER SIZE CIRCUIT FOR OFFICE UNIT.