Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00CM00340
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE. | |
11/09/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*CONDENSATE DRAIN TO AH-1 MUST BE SAME SIZE AS OUTLET ON UNIT. CANNOT BE REDUCED TO 3/4" PLUG EXTRA OUTLET ON AH 1 & 2. LOCATE SECONDARY PAN UNDER UNIT ON AH-2. | |
10/19/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*REMOVE UNION FROM GAS PIPE ON ROOF TO RUBIOS 2 UNITS ON ROOF SE-1 & SE-2 DUCT NOT INSULAED. STILL NEED TO SEE 2 AIR HANDLERS. | |
08/07/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
08/06/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1.) FINISH CONDENSATE DRAINS ON ROOF. 2.) NEED TO SEE CONDENSATE DRAINS ON WALK IN COOLERS LABEL CONDENSORS ON ROOF FOR ICE MACHINES. 3.) PROVIDE SMOKE DETECTOR TO FCU 3 & 4 4.) HOOK UP CONTROL WIRING TO FCU 1 & 2 OK FOR C OF O IN ALL THEATERS. NEED TO SEE AIR HANDLER ABOVE OFFICES. | |
07/13/2000 | MECHANICAL - FINAL | Partial Approval | OK FOR TEMP C OF O STILL NEED TO SEE A/C SYSTEM IN OFFICE & SOUTH EXIT CORRIDOR NEED TO SEE PROPER SIZE CIRCUIT FOR OFFICE UNIT. |