Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/21/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE. |
| 11/09/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*CONDENSATE DRAIN TO AH-1 MUST BE SAME SIZE AS OUTLET ON UNIT. CANNOT BE REDUCED TO 3/4" PLUG EXTRA OUTLET ON AH 1 & 2. LOCATE SECONDARY PAN UNDER UNIT ON AH-2. |
| 10/19/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*REMOVE UNION FROM GAS PIPE ON ROOF TO RUBIOS 2 UNITS ON ROOF SE-1 & SE-2 DUCT NOT INSULAED. STILL NEED TO SEE 2 AIR HANDLERS. |
| 08/07/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 08/06/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) FINISH CONDENSATE DRAINS ON ROOF. 2.) NEED TO SEE CONDENSATE DRAINS ON WALK IN COOLERS LABEL CONDENSORS ON ROOF FOR ICE MACHINES. 3.) PROVIDE SMOKE DETECTOR TO FCU 3 & 4 4.) HOOK UP CONTROL WIRING TO FCU 1 & 2 OK FOR C OF O IN ALL THEATERS. NEED TO SEE AIR HANDLER ABOVE OFFICES. |
| 07/13/2000 |
MECHANICAL - FINAL |
|
Partial Approval |
OK FOR TEMP C OF O STILL NEED TO SEE A/C SYSTEM IN OFFICE & SOUTH EXIT CORRIDOR NEED TO SEE PROPER SIZE CIRCUIT FOR OFFICE UNIT. |