Permit: DP22-0188

Parcel: 11918030A

Inspection Status: Not Ready

Inspection History: ENGR - Drainage Structures

Permit Number - DP22-0188

Inspection Description - ENGR - Drainage Structures

Inspection Status - Not Ready

Date Description Inspector Results Comments
01/02/2024 ENGR - Drainage Structures Not Ready This is for a wall inspection which will be handled by building.
01/24/2024 ENGR - Drainage Structures Not Ready Spoke with Shawn explained to him that he needs to call building inspections to have screen wall rebar inspected.
03/13/2024 ENGR - Drainage Structures Partial Pass Headwall Floor and toe down located on NE corner of site has all horizontal #4 rebar 12” oc and #4 vertical vertical rebar for toe down in place and is ok to pour the 30’ - 10” X 9’ area.

Wing walls to be viewed toward the end of the week.
03/19/2024 ENGR - Drainage Structures Partial Pass Upper bottom of head wall on the north west corner outside of the main surrounding main walls. Partial pass left open for futuer inspections
03/21/2024 ENGR - Drainage Structures Not Ready Will recall for tomorrow (Per Shawn)
03/22/2024 ENGR - Drainage Structures Partial Pass Viewed outlet headwall and sidewalls all # 4 & # 6 vertical and horizontal rebar is per plan and all snap ties for plywood are in place and ready for pour on Monday the 25th.
03/27/2024 ENGR - Drainage Structures Partial Pass Viewed West storm water CRP collar (3) #4 rebar 12” oc for inlet tying into existing CRP. (Okay to pour)
04/02/2024 ENGR - Drainage Structures Partial Pass West CRP drainage pipe tying into existing CRP running West across Cottonwood lane viewed #4 rebar floor 12” oc and #5 vertical rebar is ready for concrete pour.
04/05/2024 ENGR - Drainage Structures Partial Pass Viewed 23’ outlet headwall located in West channel of site all #4 vertical and horizontal rebar 8”oc is present and all snap ties are in place and ready for concrete pour.
05/30/2024 ENGR - Drainage Structures Passed
12/19/2023 ENGR - Drainage Structures Partial Pass viewed and verified 360’ of North wall footing all Horizontal #5 Trans Bars and #5 Long Bott bars are present and completed per approved plan and all #5 vertical wall reinforcement is in place and per approved plan detail.

3rd party Engineer inspection has also been completed and footer to be poured in a.m. 12/20/23