Inspection History: For trash and recycling enclosures
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2026 | For trash and recycling enclosures | Not Ready | Not ready due to rain yesterday/this morning. | |
| 05/08/2026 | For trash and recycling enclosures | Re-inspection required | NW dumpster enclosure: footing depth and width are okay. TSM 8-01.9.2 requires 2 #4 bars continuous the length of the footing and vertical reinforcement every 32", current configuration has only 1 continuous bar and 48" OC verts. Also need 2 vertical bars (1 per cell) at the front (east) ends of the wall. Needs to be corrected and reinspected before pouring. | |
| 05/15/2026 | For trash and recycling enclosures | Partial Pass | 6' Wall/Footers built to detail 109 in bldg. plans. (Site screen walls and Refuse enclosures) NE Refuse enclosure footer OK to pour with two rebar's at the end of the wall Add rebars to ends of walls so there are at 2 NW at gate ends of walls. |
|
| 06/25/2026 | For trash and recycling enclosures | Partial Pass | good to grout the trash enclosure at the north east corner of the property at the 4 foot mark | |
| 07/15/2026 | For trash and recycling enclosures | Partial Pass | NW corner refuse enclosure: slab sub-grade and reinforcement are good. Okay to pour. | |
| 07/28/2026 | For trash and recycling enclosures | Partial Pass | NE corner & N middle refuse enclosure: slab sub-grade and reinforcement are good. Okay to pour. |