Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Partial Pass
Inspection History
| Date |
Description |
Inspector |
Results |
Comments |
| 04/24/2026 |
|
|
Partial Pass |
Ramada between bldgs. 2, 3, & 4: four footing, dimensions and reinforcements are good, okay to pour. |
| 05/08/2026 |
|
|
Re-inspection required |
Site wall along North border: Vertical reinforcement is set up at 48" OC, plan details require 32" OC. Needs to be corrected and reinspected before pouring. |
| 05/13/2026 |
|
|
Partial Pass |
Footer for single screen wall and refuse enclosure at North west corner of site. West Screen wall runs from RE at corner approximately 300’ South. Footer for both wall and RE are correct to detail 109. 6’ Masonary wall & footing. Okay to pour this footer for wall and Refuse enclosure. Schedule inspection when ready with #5 bond beam at grade for pre grout |
| 05/18/2026 |
|
|
Partial Pass |
The photo for the trash enclosure needs two number four bars at the front one on each end before they can pour contractor said he would take photos and send them to us |
| 11/20/2025 |
|
|
Not Ready |
Scheduled to view permit history |