Inspection Status: Partial Pass
Inspection History
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2026 |
|
|
Partial Pass |
Wall at clubhouose firepit: reinforcement is good. Okay to grout. |
| 04/24/2026 |
|
|
Partial Pass |
Ramada between bldgs. 2, 3, & 4: four footing, dimensions and reinforcements are good, okay to pour. |
| 05/08/2026 |
|
|
Re-inspection required |
Site wall along North border: Vertical reinforcement is set up at 48" OC, plan details require 32" OC. Needs to be corrected and reinspected before pouring. |
| 05/13/2026 |
|
|
Partial Pass |
Footer for single screen wall and refuse enclosure at North west corner of site. West Screen wall runs from RE at corner approximately 300’ South. Footer for both wall and RE are correct to detail 109. 6’ Masonary wall & footing. Okay to pour this footer for wall and Refuse enclosure. Schedule inspection when ready with #5 bond beam at grade for pre grout |
| 05/18/2026 |
|
|
Partial Pass |
The photo for the trash enclosure needs two number four bars at the front one on each end before they can pour contractor said he would take photos and send them to us |
| 06/02/2026 |
|
|
Partial Pass |
good to grout the west wall 200 lineal feet 6 foot tall |
| 08/06/2026 |
|
|
Partial Pass |
Carport 10: footings on North side, 4 sections, 20 total footings, dimensions and separation are good. Okay to pour 20 footings. |
| 08/07/2026 |
|
|
Partial Pass |
Okay to pour south foundations. submit details to portal, separate permits should be issued. |
| 11/20/2025 |
|
|
Not Ready |
Scheduled to view permit history |