Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Passed
Inspection History: ENGR Grading Final
| Date |
Description |
Inspector |
Results |
Comments |
| 02/06/2017 |
ENGR Grading Final |
MRUSSO |
Approved |
Entered by DROBERT5 - |
| 02/06/2017 |
ENGR Grading Final |
MRUSSO |
Approved |
Entered by DROBERT5 - |
| 01/31/2017 |
ENGR Grading Final |
DROBERTS |
Continued |
Entered by DROBERT5 - MET WITH THE DEVELOPER AND LOOKED AT THE SIDEWALK AND WITHIN THE RIGHT OF WAY AND INTO THE SITE. SOME OF THE AREAS EXCEED THE MAXIMUM 2% CROSS SLOPE WITHIN THE RIGHT OF WAY, AND THE RUNNING SLOPES INTO THE PROPERTY EXCEEDS THE 5%. I CHECKED ALL THE SLOPES WITH THE AUTOLEVEL AND WITH THE LASER TO SEE WHAT NEEDS CAN BE ADDRESSED PRIOR TO REQUESTING THE FINAL INSPECTION FOR THIS SITE. I ADVISED THE CONTRACTOR THAT THEY WILL BE REQUIRED TO INSTALL HANDRAILS IN ALL AREAS THAT EXCEED 5% IN THE RUNNING SLOPE. |
| 01/19/2017 |
ENGR Grading Final |
MRUSSO |
Continued |
Entered by DROBERT5 - NO SIGNIFICANT STORM WATER CONCERNS AT THIS TIME |
| 02/06/2017 |
ENGR Grading Final |
MRUSSO |
Approved |
Entered by DROBERT5 - |
| 02/02/2017 |
ENGR Grading Final |
MRUSSO |
Continued |
Entered by DROBERT5 - SPOKE WITH SUPERINTENDENT ABOUT ADA ACCESS FROM THE STREET TO THE BLDG |
| 01/31/2017 |
ENGR Grading Final |
DROBERTS |
Continued |
Entered by DROBERT5 - MET WITH THE CONTRACTOR AND LOOKED AT THE SIDEWALK AND WITHIN THE RIGHT OF WAY AND INTO THE SITE. SOME OF THE AREAS EXCEED THE MAXIMUM 2% CROSS SLOPE WITHIN THE RIGHT OF WAY, AND THE RUNNING SLOPES INTO THE PROPERTY EXCEEDS THE 5%. I CHECKED ALL THE SLOPES WITH THE AUTOLEVEL AND WITH THE LASER TO SEE WHAT NEEDS CAN BE ADDRESSED PRIOR TO REQUESTING THE FINAL INSPECTION FOR THIS SITE. I ADVISED THE CONTRACTOR THAT THEY WILL BE REQUIRED TO INSTALL HANDRAILS IN ALL AREAS THAT EXCEED 5% IN THE RUNNING SLOPE. |
| 01/31/2017 |
ENGR Grading Final |
MRUSSO |
Continued |
Entered by DROBERT5 - 1) PEDESTRIAN ACCESS FROM THE STREET TO THE BLDG HAS A SLOPE GREATER THAN 5% BUT LESS THAN 8.3 %. SIDEWALK ACCESS MUST HAVE RAILING ON BOTH SIDES, A LANDING ON BOTH SIDES AND NOT RISE MORE THAN 30" AT A TIME PER ADA.
2) HC PARKING MUST MEET ADA. LOADING AREA MUST BE FLAT AND ACCESS RAMP MUST BE THE SAME WIDTH OF THE LOADING AREA |
| 12/08/2016 |
ENGR Grading Final |
MRUSSO |
Continued |
Entered by MRUSSO1 - RE-BAR LAYOUT AND FOOTING FOR SCREEN WALL INSTALLED PER APPROVED PLAN (COT STD DETAIL 109) |
| 12/01/2016 |
ENGR Grading Final |
MRUSSO |
Continued |
Entered by MRUSSO1 - REVIEW OF GRADING PLANS AND MET W/ SUPERINTENDENT
CALL FOR INSPECTION FOR ANY SITE CONCERNS OR CHANGES |
| 02/06/2017 |
ENGR Grading Final |
MRUSSO |
Approved |
Entered by DROBERT5 - |
| 12/08/2016 |
ENGR Grading Final |
MRUSSO |
Continued |
Entered by MRUSSO1 - RE-BAR LAYOUT AND FOOTING FOR SCREEN WALL INSTALLED PER APPROVED PLAN (COT STD DETAIL 109) |